Burner Sizing Formulas and Worked Example
This is a formula reference for early sizing. It distinguishes fuel heat input from useful heat output so that efficiency is not applied twice.
Heat input and useful output
Q_in = fuel_rate × heating_value Q_out = Q_in × efficiency fuel_rate = Q_in / heating_value fuel_rate = Q_out / (heating_value × efficiency)
Q_in is fuel heat input; Q_out is useful heat delivered. Use the same lower-heating-value (LHV) or higher-heating-value (HHV) basis for both heating value and efficiency. Efficiency is a fraction, such as 0.80, not 80.
Illustrative example
Assume a useful output of 800 kW, an LHV of 10 kWh/Nm³ and an efficiency of 0.80 on that same basis. Required heat input is 800 / 0.80 = 1,000 kW. Fuel flow is 1,000 / 10 = 100 Nm³/h. These assumed values illustrate the calculation; they are not a recommended fuel value or equipment rating.
For gas volumes, specify the reference temperature and pressure. For mass-based heating value in kWh/kg, the resulting flow is kg/h. Convert units before comparing figures.
Turndown
turndown = maximum stable firing rate / minimum stable firing rate
Use rates measured on the same basis. Check the firing diagram, furnace backpressure and low-load stability before choosing a burner.